Three Phase to Single Phase.
Advanced Electronic Protection for device safety with MCB & fast acting fuses
TECHNOLOGY | DSP based, IGBT inverter ‐ IGBT converter Online UPS |
RATING | 10 KVA ‐ 40 KVA |
DC BUS | 240 VDC ‐ 360 VDC |
INPUT | |
Input Voltage | 415 VAC, 3 Wire (RYB) & N |
Input Voltage Window | 330 VAC ‐ 470 VAC |
Input Frequency | 45 ‐ 55 Hz |
Input PFC | 100 % load | > 0.95 |
Power walk in | Soft start for 0‐20 seconds power walk ‐ in |
RECTIFIER | |
Type | IGBT based full bridge |
Ripple Voltage | < 2 % |
Converter Protection | Advanced Electronic Protecon for device safety with MCB & fast acng fuses |
INVERTER | |
Inverter Type | IGBT based MPWM with instantaneous Sinewave Control |
Output PF | 0.8 lagging to Unity |
Nominal Voltage | 230 VAC, 1 , P‐N |
Regulation | (+/-)1% |
Frequency | 50 Hz (+/-) 0.1 Hz |
Waveform | True Sinewave |
Total Harmonic | Linear Load | < 2% |
Distortion | Non Linear Load | < 5% |
Transient Response | Remains within +/‐ 5% & recover to normal within 20 msec |
Over Load | 100 % | Continuous |
Capacity | 110% | 5 Minutes |
Crest Factor | 3 : 1 |
Mode of Operation | Designed for Continuous operation |
ISOLATION | True Online with complete galvanic isolation |
Inverter Protection Advanced Electronic Protection for device safety with MCB & fast acting fuses, high speed pulse by pulse electronic device protection over voltage / under voltage protection, Electronic over current trip. | |
BYPASS | |
Manual Bypass | Provided |
ALARMS | |
Input / Low / Fail Output overload / Over temperature / Battery low | |
LED Indications (Single LED with multi function) | |
Mains on / UPS on / Battery Low Overload | |
Input Voltage / Output Voltage / Load current / Output Frequency / Battery Voltage | |
OPTIONAL | Static Bypass, SNMP, GSM based SMS Monitoring, RS 232, RS 485 MODBUS |